Boiler Pressure Switches

Dungs Climate set, Differential Pressure Switch for air

Available to order MODEL KS 600 A2-7

Two separate pressure chambers with pressure-side connection to hose nipples. Connection of ø 4 mm for each pressure chamber. Reference value (pressure difference) can be set directly. Reference value can be read off externally through the transparent hood. Precise function thro...

Supplied by FieldInstruments.lk Sri Lanka office · global sourcing network
Delivery time Confirmed with your quotation, based on availability
Freight & applicable duties Extra. Final costs will be provided with your quotation.
Need delivery to another country? Contact us for availability and delivery options.
Contact us

General

Two separate pressure chambers with pressure-side connection to hose nipples. Connection of ø 4 mm for each pressure chamber. Reference value (pressure difference) can be set directly. Reference value can be read off externally through the transparent hood. Precise function through special switching system in a frictionless bearing. Contact switchover is performed when the set reference value is exceeded or undershot. Complete mounting kit enclosed.

Application

The equipment is used in ventilation and air-conditioning systems, DDC. It is specially designed for monitoring air ducts, filters, drive units and blowers.

Specifications

  • Make: DUNGS
  • Part Number: KS 600 A2-7
  • Order Number: 257 844
  • Setting range in. W.C: 30-600
  • Max. operating pressure: 10 kPa (100 mbar)
  • Pressure connection: Hose connector for hose ø 4
  • Switching voltage: Au contact DC min. 5 V max. 24 V
  • Nominal current: Au contact DC 20 mA
  • Switching current: Au contact DC min. 5 mA max. 20 mA
  • Electrical connection: On terminal screws via cable duct M20 x 1,5
  • Protection type: IP 54 as specified in IEC 529 (EN 60529), optional IP 65
  • Setting tolerance: see setting range page 4, switching point deviation, relative to nominal value, with vertical mounting position. Rising (↑) or falling (↓) setting available on site.
  • Deviation: Permissible deviation of the set value ≤ ± 15 % in the service life test according to EN 1854