Dungs Differential Pressure Switch for air, flue and exhaust gases

Available to order MODEL LGW 3 A2

The differential pressure switches LGW…A2… are adjustable differential pressure switchesas per EN 1854 for automatic burner controls. Suitable for switching a circuit on, off or over on changes in actual pressure value relative to the set reference value. The reference value (swi...

Supplied by FieldInstruments.lk Sri Lanka office · global sourcing network
Delivery time Confirmed with your quotation, based on availability
Freight & applicable duties Extra. Final costs will be provided with your quotation.
Need delivery to another country? Contact us for availability and delivery options.
Contact us

General

The differential pressure switches LGW…A2… are adjustable differential pressure switchesas per EN 1854 for automatic burner controls. Suitable for switching a circuit on, off or over on changes in actual pressure value relative to the set reference value. The reference value (switching point) is adjusted on a setting wheel provided with a scale. On LGW…A2P: test button integrated in lower part as standard.

Application

Differential pressure monitoring in firing, ventilation and air-conditioning systems. Suitable for air, flue and exhaust gases and other non-aggressive gases as differential pressure switches; not suitable for industrial combustion gases.

Specifications

  • Make: DUNGS
  • Part Number: LGW 3 A2
  • Order Number: 272337
  • Setting range (mbar):0.4-3
  • Max. operating pressure: 500 mbar (50 kPa)
  • Pressure connection: hose gland ø 4.6 mm
  • Switching voltage:
        • Ag contact AC eff. min. 24 V max. 250 V
        • DC min. 24 V max. 48 V
        • Au contact DC min. 5 V max. 24 V
  • Nominal current: AC eff. 10 A
  • Electrical connection: Standard At screw terminals via M20x1.5 cable entry Special design Plug connection for line sockets as per DIN EN 175 301-803, 3-pin
  • Degree of protection: IP 54 IEC 529 (EN 60529), protection insulated, optional IP 65
  • Setting tolerance: ± 15 % switching point deviation, relative to nominal value, with vertical mounting position. Rising (↑) or falling (↓) setting available on site.
  • Deviation: Permissible deviation of the set value ≤ ± 15 % in the service life test according to EN 1854