Duct Air Quality Sensors & Transmitters

Greystone AQDTB008Duct Air Quality Transmitter (VOC)

Available to order MODEL AQDTB08

The duct indoor air quality sensor uses an advanced MEMS metal oxide semiconductor sensor to detect poor air quality. The sensor reacts quickly to detect a broad range of VOCs such as smoke, cooking odors, bio-effluence, outdoor pollutants and from human activities. The sensor ca...

Supplied by FieldInstruments.lk Sri Lanka office · global sourcing network
Delivery time Confirmed with your quotation, based on availability
Freight & applicable duties Extra. Final costs will be provided with your quotation.
Need delivery to another country? Contact us for availability and delivery options.
Contact us

General

The duct indoor air quality sensor uses an advanced MEMS metal oxide semiconductor sensor to detect poor air quality. The sensor reacts quickly to detect a broad range of VOCs such as smoke, cooking odors, bio-effluence, outdoor pollutants and from human activities. The sensor captures all VOC emissions that are completely invisible to CO2 sensors. A weatherproof polycarbonate enclosure is provided for ease of installation.

Features

  • True Air Quality Monitor
  • Microprocessor based controller
  • Linear and stepped analog output
  • Optional relay output
  • Optional temperature sensor
  • LCD Display
  • Polycarbonate enclosure with hinged and gasketed cover

Specifications

  • Make: Greystone
  • Model: AQDTB08
  • Sensor Technology:           MEMS metal oxide semiconductor VOC sensor
  • Measurement Range: 450-2000 ppm CO2 equivalent or 0-100% (menu selectable)
  • Drift Compensation: Automatic baseline correction
  • Power Supply:          20-28 Vac/dc (non-isolated half-wave rectified)
  • Consumption : 35 mA max @ 24 Vdc
  • Input Voltage Effect: Negligible over specified operating range
  • Protection Circuitry: Reverse voltage protected, over voltage protected
  • Operating Conditions: 0 to 50°C (32 to 122°F), 5 to 95 %RH non-condensing
  • Linear Output Signal: 0-5 / 0-10 Vdc (menu selectable) = 0-2000 ppm CO2 equivalent
  • Analog Stepped Output Signal: Three steps representing Good, Fair, and Poor air quality (each step is independently adjustable from 0-10 Vdc)
  • Output Drive Capability: 10,000 Ω minimum
  • Programming And Selection: Via internal push-buttons and LCD menu
  • Warm-Up Time: 5 minutes
  • LCD Resolution: 1 ppm / 1%
  • LCD Size: 35mm W x 15mm H (1.4” x 0.6”) alpha-numeric 2 line x 8 characters
  • Wiring Connections: Screw terminal block (14 to 22 AWG)
  • Duct Probe: 152mm L x 22.5mm D (6” x 0.88”)
  • Optional Temperature Sensor: 2.25K Ohm, NTC Thermistor
  • Options:
  •  Enclosure: Polycarbonate UL94-V0, IP65
  • Dimensions: 116.5mm W x 99.7mm H x 53.7mm D (4.58” x 3.93” x 2.11”)
  • Country of Origin: Canada