Greystone - Greystone DPB04S15 Differential Pressure Transmitter


Greystone DPB04S15 Differential Pressure Transmitter - DPB04S15

Product Greystone DPB04S15 Differential Pressure Transmitter
Brand Greystone
Product Price 0 LKR
Datasheet Download

Description

General

The differential pressure transmitter is designed with dual remote sensors that enable it to accept high pressure in ranges up to 500 PSI. All models are rated for overload pressure 2X the maximum fully scale range and burst pressure is 5X the maximum full scaled range. Features include field selectable pressure ranges and output signal types, output reversal and slow damping, port swapping and bidirectional measurements for the most flexible applications. The output signal is factory calibrated and temperature compensated for the highest start-up accuracy.

Features

  • FT-6 or Armoured cable available in different lengths
  • Switch selectable uni or bi-directional
  • Hinged Polycarbonate weatherproof enclosure

Specifications

  • Make: Greystone
  • Model: DPB04S15
  • Range: 0 to 50,100,250, and 500 PSI range
  • Cable: FT-6 Plenum Rated, 1.5M (5')
  • Power Supply: 24 Vac/dc ±10% (non-isolated, half-wave rectified)
  • Consumption: 75 mA max @ 24 Vdc
  • Output signal: 4-20 mA sourcing, 0-5/0-10 Vdc (switch selectable)
  • Protection circuitry: Reverse voltage protected, transient protected
  • LCD display: 35mm x 15mm (1.4” x 0.6”), 2 line x 8 character
  • Accuracy: ±1% F.S. of selected range (range 4 is ± 2% F.S.) @ 22°C (72°F) including hysteresis,
  • non-linearity and repeatability
  • Stability: ±0.25% FS typical (1 year)
  • Pressure ranges: 4 per model (menu selectable)
  • Media compatibility: 17-4 PH stainless steel
  • Proof pressure: 2X highest range per model
  • Burst pressure: 20X highest range per model
  • Maximum line pressure: = highest model range
  • Pressure cycles: >100 million
  • Surge dampening: 1-60 seconds averaging (menu selectable)
  • Zero adjust: Push-button and remote input
  • Sensor operating range: -40 to 105°C (-40 to 221°F)
  • Operating environment: 0 to 50°C (32 to 122°F), 10 to 90 %RH non-condensing
  • Pressure connection: 1/4” NPT male
  • Sensor housing: IP67

Contacts and Delivery

Fieldinstruments.lk
50/3, Angampitiya Rd, Ethul Kotte, Sri Lanka. 10100.