General The HONEYWELL C6097A1103 is a diaphragm-actuated gas pressure switch designed to monitor high gas and air pressure in industrial combustion and burner control systems. It features an adjustable operating pressure range of 1.5 to 7 psi (10.3 to 48 kPa) and manual reset ope...

Supplied by FieldInstruments.lk Sri Lanka office · global sourcing network
Delivery time Confirmed with your quotation, based on availability
Freight & applicable duties Extra. Final costs will be provided with your quotation.
Need delivery to another country? Contact us for availability and delivery options.
Contact us

General
The HONEYWELL C6097A1103 is a diaphragm-actuated gas pressure switch designed to monitor high gas and air pressure in industrial combustion and burner control systems. It features an adjustable operating pressure range of 1.5 to 7 psi (10.3 to 48 kPa) and manual reset operation.

This model uses a flange-mounted configuration for installation on compatible Honeywell integrated valve trains. When the monitored pressure falls below the selected switching point, the switch interrupts the electrical control circuit and remains locked out until manually reset.

Features
- Adjustable pressure range from 1.5 to 7 psi
- Manual reset operation
- Flange-mounted installation
- Diaphragm-actuated safety-limit switch
- Additive switching differential
- Switches on falling pressure
- Suitable for gas and air pressure monitoring
- Adjustable switching point
- Designed for industrial burner and combustion systems

Key Specifications
Pressure Specifications
- Model: C6097A1103
- Operating pressure range: 1.5 to 7 psi
- Operating pressure range: 10.3 to 48 kPa
- Maximum manual reset differential at minimum setpoint: 1.1 psi (7.6 kPa)
- Maximum manual reset differential at maximum setpoint: 1.4 psi (9.6 kPa)
- Differential type: Additive
- Maximum rated continuous pressure: 9.3 psi
- Reset type: Manual reset

Mounting Specifications
- Mounting type: Flange mount
- Installation: Compatible Honeywell integrated valve train
- Pressure connection: Flange-mounted configuration

Electrical Specifications
- Switch action: Breaks the control circuit on pressure fall
- Contact arrangement: SPDT
- Inductive full-load current: 3 A
- Inductive locked-rotor current: 18 A
- Resistive current: 5 A

Environmental Specifications
- Ambient temperature range: -40°F to +140°F (-40°C to +60°C)

Dimensions
- Height: Approximately 90 mm
- Width: Approximately 69 mm
- Depth: Approximately 69 mm

Approvals
- UL Listed
- CSA Listed
- FM Approved