Boiler Pressure Switches

HONEYWELL C6097A1228 Gas Pressure Switch – 0.4 to 5 in. wc Pressure Range, Flange-Mounted, Manual Reset

Available to order MODEL C6097A1228

General The HONEYWELL C6097A1228 is a diaphragm-actuated gas pressure switch designed to monitor low gas and air pressure in industrial combustion and burner control systems. It features an adjustable pressure range of 0.4 to 5 in. wc (0.10 to 1.25 kPa) and manual reset operation...

Supplied by FieldInstruments.lk Sri Lanka office · global sourcing network
Delivery time Confirmed with your quotation, based on availability
Freight & applicable duties Extra. Final costs will be provided with your quotation.
Need delivery to another country? Contact us for availability and delivery options.
Contact us

General
The HONEYWELL C6097A1228 is a diaphragm-actuated gas pressure switch designed to monitor low gas and air pressure in industrial combustion and burner control systems. It features an adjustable pressure range of 0.4 to 5 in. wc (0.10 to 1.25 kPa) and manual reset operation.

This model features a flange-mounted configuration for direct installation on compatible Honeywell integrated valve trains. When the monitored pressure falls below the selected switching point, the switch interrupts the electrical control circuit and remains locked out until manually reset.

Features
- Adjustable pressure range from 0.4 to 5 in. wc
- Manual reset with external reset button
- Flange-mounted installation
- Diaphragm-actuated safety-limit switch
- Additive switching differential
- Breaks the control circuit on pressure fall
- Suitable for natural gas, LP gas and air
- Adjustable switching point
- Transparent protective cover for adjustment scale and knob
- Integrated surge orifice and vent limiter
- IP54 enclosure protection

Key Specifications
Pressure Specifications
- Model: C6097A1228
- Operating pressure range: 0.4 to 5 in. wc
- Operating pressure range: 0.10 to 1.25 kPa
- Maximum differential at minimum setpoint: 0.6 in. wc (0.15 kPa)
- Maximum differential at maximum setpoint: 0.25 in. wc (0.25 kPa as published)
- Differential type: Additive
- Maximum rated continuous pressure: 2.9 psi
- Reset type: Manual reset

Mounting and Connections
- Mounting type: Flange mount
- Installation: Direct mounting on compatible Honeywell integrated valve train
- Vent / low-pressure connection: 1/8-inch NPT internal thread

Electrical Specifications
- Switching action: Breaks NO-to-C connection on pressure fall
- Contact arrangement: SPDT
- Electrical rating: 120/240 VAC, 50/60 Hz
- Inductive full-load current: 3 A
- Inductive locked-rotor current: 18 A
- Resistive current: 5 A

Environmental Specifications
- Ambient temperature range: -40°C to +60°C
- Enclosure protection: IP54

Dimensions
- Height: 90 mm
- Width: 69 mm
- Depth: 69 mm

Approvals
- UL Listed
- CSA Listed
- FM Approved
- CSD-1 AFB Acceptable