General The HONEYWELL C6097B1051 is a diaphragm-actuated gas pressure switch designed to monitor high gas and air pressure in industrial combustion and burner control systems. It features an adjustable pressure range of 1.5 to 7 psi (10.3 to 48 kPa) and manual reset operation.
General
The HONEYWELL C6097B1051 is a diaphragm-actuated gas pressure switch designed to monitor high gas and air pressure in industrial combustion and burner control systems. It features an adjustable pressure range of 1.5 to 7 psi (10.3 to 48 kPa) and manual reset operation.
This model features a 1/4-inch NPT pipe connection for pressure monitoring installations. Unlike C6097A models, which switch on falling pressure, the C6097B1051 operates on rising pressure. When pressure reaches the selected switching point, the switch interrupts the electrical control circuit and remains locked out until manually reset.
Features
- Adjustable pressure range from 1.5 to 7 psi
- Manual reset with external reset button
- 1/4-inch NPT pressure connection
- Diaphragm-actuated safety-limit switch
- Subtractive switching differential
- Breaks the control circuit on pressure rise
- Suitable for natural gas, LP gas and air
- Can be wired to activate an alarm or safety control circuit
- Transparent protective cover for adjustment scale and knob
- Integrated surge orifice and vent limiter
- IP54 enclosure protection
Key Specifications
Pressure Specifications
- Model: C6097B1051
- Operating pressure range: 1.5 to 7 psi
- Operating pressure range: 10.3 to 48 kPa
- Manual reset differential at minimum setpoint: 1.1 psi (7.6 kPa)
- Manual reset differential at maximum setpoint: 1.4 psi (9.6 kPa)
- Differential type: Subtractive
- Maximum rated continuous pressure: 9.3 psi
- Reset type: Manual reset
Mounting and Connections
- Mounting type: Pipe mount
- Main pressure connection: 1/4-18 NPT internal thread
- Vent / low-pressure connection: 1/8-27 NPT internal thread
- Differential pressure connection: Suitable for air-only applications
Electrical Specifications
- Contact arrangement: SPDT
- Switching action: Breaks normally closed (NC) to common (C) connection on pressure rise
- Electrical rating: Refer to the applicable Honeywell C6097A/B electrical rating documentation
Environmental Specifications
- Ambient temperature range: -40°C to +60°C
- Enclosure protection: IP54
Dimensions
- Height: 81 mm
- Width: 69 mm
- Depth: 69 mm
Approvals
- UL Listed
- CSA Listed
- FM Approved
- IRI Acceptable
- CSD-1 AFB Acceptable
FieldInstruments.lk
International Inquiries:
Xelexon International (Pvt) Ltd
510, Level 05, Jana Jaya City, Rajagiriya, Sri Lanka 10100
Local Inquiries:
Nexus Engineering Solutions Pvt Ltd
237, Raja Maha Vihara Rd, Mirihana, Pitakotte, Sri Lanka 10100
Testing & Measuring Instruments:
Instrumentation Solutions (Pvt) Ltd
510, Level 05, Jana Jaya City, Rajagiriya, Sri Lanka 10100
Delivery time, freight and applicable duties are confirmed with your quotation.