Honeywell - Honeywell C7027A Minipeeper® Ultraviolet Flame Detector

Honeywell


Honeywell C7027A Minipeeper® Ultraviolet Flame Detector - C7027A1049/U

Product Honeywell C7027A Minipeeper® Ultraviolet Flame Detector
Brand Honeywell
Product Price 0 LKR
Datasheet Download

Description

General

The C7027A, C7035A, C7044A and C7927A Minipeeper® Ultraviolet Flame Detectors detect the ultraviolet radiation emitted by combustion flames. The flame detectors are used with Honeywell flame safeguard controls to provide flame supervision for gas, oil, or combination gas-oil burners.

Features

  • C7027A, C7035A, and C7044A Flame Detectors are used with RA890G devices or R7249A, R7290A, R7749B and R7849A,B Amplifiers and the appropriate Honeywell controls.
  • C7927A is used with only the R7851B Flame Amplifier and the 7800 SERIES controls.
  • C7044A may also be used with the following 50 Hz Honeywell combustion controls/amplifiers:— R4341/R7323, — R4343/R7323, — R4344/R7323
  • C7027A/C7927A has an integral collar threaded (internal 1/2-14 NPSM) for mounting on a one-half-inch sight pipe.
  • C7035A has an integral collar threaded (internal 1-11-1/2 NPSM) for mounting on a one-inch sight pipe.
  • C7035A housing meets Underwriters Laboratories Inc. requirements for rain tightness and complies with NEMA enclosure standards, types 4 and 4X.
  • C7044A mounts with a two screw bracket. The UV sensor tube is enclosed in a stainless steel housing.
  • C7044A has the capability of side or end viewing in flame monitoring applications.
  • Because of its compact size, the C7044A is particularly suitable for blast tube mounting.
  • Properly installed, the C7027A, C7035A and C7927 are pressure rated for 5 psi.
  • C7035A ultraviolet radiation sensor tube is field replaceable.
  • Two C7027A, C7035A or C7044A Flame Detectors can be wired in parallel for difficult flame sighting installations. (C7927cannot be used in parallel.)
  • C7927A, C7027A1049, C7027A1064, C7027A1072 come with 1/2-in. spud connection for electrical wiring.

Specifications

  • Make:  Honeywell
  • Model: C7027A1049/U
  • Ambient Operating Temperature Ratings: 0°F to 215°F (-18°C to 102°C), or -40°F to 215°F (-40°C to +102°C), depending on model.
  • Maximum Pressure Rating: 5 psi (34.5 kPa).
  • Mounting: Collar with 1/2-14 NPSM internal threads for mounting on a 1/2 in. sight pipe.
  • Wiring Connections: Two 8 ft (2.44 m), color-coded, Plastic-insulated, 18 AWG, NEC Class 1 lead wires, rated for 221°F (105°C). (C7027A1064 has 24 ft [7.32 m]
  • Lead wires.) Rear of detector has a clamp type connector for 1/2 in. flexible metallic conduit. (Models are available with 1/2 in. internally threaded spud connector instead of the clamp). C7027A1114 has 44 in. (1.118 m) lead wires and 22 in. (558 mm) flexible conduit.

Contacts and Delivery

Fieldinstruments.lk
50/3, Angampitiya Rd, Ethul Kotte, Sri Lanka. 10100.
Phone: +94718555888 Email: info@fieldinstruments.lk