General
The M7281, M7282, M7284, M7285 and M7294 are Electronic Modutrol® Motors used to control dampers and valves. These motors accept a current signal from an electronic controller to position a damper or valve at any position between open and closed..
Features
- Replace M744S,T,Y and M745S,T,Y Motors.
- M7284, M7281 are 150 lb.-in. non-spring return; M7294 is 300 lb.-in. non-spring return; M7285, M7282 are 60 lb-in. spring return.
- Oil immersed motor and gear train for reliable performance and long life.
- Wiring box provides NEMA 3 weather protection.
- Quick-connect terminals standard—screw terminal adapter available.
- Adapter bracket for matching shaft height of older motors is standard with replacement motors.
- Die cast aluminum housing.
- Models available with integral auxiliary switches.
- Models available with adjustable zero and span..
Specifications
- Make: Honeywell
- Model: M7284A1004/U
- Integral spring return returns motor to normal position in the event of
- power failure on spring return models.
- Integral junction box provides NEMA 3 weather protection if motor is mounted in the upright position.
- Motor and circuitry operate from 24 Vac.
- Quick-connect terminals are standard--screw terminal adapter is available.
- Adapter bracket for matching shaft height of older motors is available.
- Motors have field adjustable stroke (90 to 160 degrees).
- Integral auxiliary switches are available factory mounted, or can be field added.
- Spring return motors can operate valve linkages from power end or auxiliary end shafts for normally closed or normally open valve applications.
- Application : Electric
- Dimensions (in.) : 6 7/16 in. high x 5 1/2 in. wide x 7 5/16 in. deep
- Dimensions (mm) : 164 mm high x 140 mm wide x 185 mm deep
- Comments : Adjustable zero and span for split range applications
- Mounting : Foot-mounted
- Frequency : 50 Hz; 60 Hz
- Approvals, Underwriters Laboratories Inc : Listed: File No. E4436,Guide No. XAPX for USA and Canada
- Electrical Connections : Screw terminals
- Supply Voltage : 120V
- Internal Auxiliary Switch : 0
- Factory Stroke Setting : 90 degrees