Honeywell - Honeywell TC847A1004 Single-Ended, Reflector-Type Addressable Beam Smoke Detector

Honeywell


Honeywell TC847A1004 Single-Ended, Reflector-Type Addressable Beam Smoke Detector - TC847A1004

Product Honeywell TC847A1004 Single-Ended, Reflector-Type Addressable Beam Smoke Detector
Brand Honeywell
Product Price 0 LKR
Datasheet Download

Description

General

The Honeywell TC847A1004 are intelligent, addressable reflected beam smoke detectors for protecting open areas with high and sloping ceilings, and wide-open areas, where spot-type smoke detectors are difficult to install and maintain. Ideal applications are atriums, cathedral ceilings, aircraft hangars, warehouses, sporting arenas, concert halls, and enclosed parking facilities. They are compatible with Honeywell’s Intelligent Fire Alarm Control Panels in FlashScan® or CLIP mode, as well as with the FS90, XLS200, and XLS1000 in CLIP mode only. Installation of the single-ended reflective design is much quicker than a dual-ended projected beam detector. Alignment is easily accomplished with an optical sight and a two-digit signal strength meter incorporated into the beam detector. Listed for operation from –22°F to 131°F, the TC847A1004 are usable in open area applications where temperature extremes exceed the design limits of other types of smoke detection.

The TC847A1004 are a transmitter/receiver unit and a reflector. When smoke enters the area between the unit and the reflector it causes a reduction in the signal strength. When the smoke level (signal strength) reaches the predetermined threshold, an alarm is activated. The detectors have four standard sensitivity selections as well as two Acclimate® settings. When either Acclimate® setting is selected, the detector’s advanced software algorithms automatically adjust to the optimum sensitivity for the specific environment.

The TC847A1004 has an integral sensitivity test feature of a filter attached to a servomotor inside the detector optics. Activation of the RTS151 or RTS151KEY remote test stations moves the filter into the pathway of the light beam, testing the detector’s sensitivity. This sensitivity test feature allows the user to quickly and easily meet the annual maintenance and test requirements of NFPA 72, without physical access to the detector. The servomotor must be powered by +24 VDC, not SLC power.

Features

  • Listed to UL 268, ULC CAN/ULC S529.
  • Transmitter/receiver built into same unit.
  • Six user-selectable sensitivity levels.
  • 16' to 328' (use BEAMLRK beyond 230') protection range.
  • Removable plug-in terminal blocks.
  • Digital display — no special tools required.
  • Built-in automatic gain control compensates for signal deteri-oration from dust buildup.
  • Optional remote test station.
  • Optional long-range kit (BEAMLRK) for applications in excess of 230' (70 m).
  • Optional multi-mount kit (BEAMMMK) providing ceiling or wall mount capability with increased angular adjustment.
  • Optional heater kits (BEAMHK and BEAMHKR) for prevention of condensation (not intended to increase or reduce the specified operating temperature).
  • Paintable cover.

Specifications

  • Make: Honeywell
  • Model: TC847A1004
  • Voltage: 15 to 32 VDC.
  • Average Standby Current  (24 VDC): 2 mA maximum (LED flashing, SLC @ 24 V).
  • Alarm Current (LED on): 8.5 mA maximum.
  • Trouble Current (LED on): 4.5 mA maximum.
  • Alignment Current: 20 mA maximum.
  • External Supply: Voltage — 15 to 32 VDC | Current — 0.5 A maximum.
  • Shipping Weight: 3.7 lbs (1.68 kg)
  • Detector Dimensions: 10.0" H x 7.5" W x 3.3" D (254 mm H x 191 mm W x 84 mm D).
  • Reflector Dimensions for 16' to 230' (5 to 70m) Applications: 7.9" x 9.1" (200 x 230 mm).
  • Reflector Dimensions for Applications Beyond 230'/70m: 15.7" x 18.1" (400 x 460 mm).
  • Temperature:  –22°F to 131°F (–30°C to 55°C).
  • Humidity: 10 – 93% RH noncondensing.

Contacts and Delivery

Fieldinstruments.lk
50/3, Angampitiya Rd, Ethul Kotte, Sri Lanka. 10100.
Phone: +94718555888 Email: info@fieldinstruments.lk