Oventrop - Oventrop 1012450 Aktor T 2P Modulating Thermal Actuators 24 V

Oventrop


Oventrop 1012450 Aktor T 2P Modulating Thermal Actuators 24 V - 1012450

Product Oventrop 1012450 Aktor T 2P Modulating Thermal Actuators 24 V
Brand Oventrop
Product Price 0 LKR
Datasheet Download

Description

General

Thermal actuators are used in the heating, ventilation and air conditioning trades. The actuators can be used for room temperature control or as zone valves. In combination with Oventrop thermostatic valves or heating circuit distributors/collectors for surface heating and Oventrop room thermostats, they enable individual room temperature control. The control can be carried out by regulation via on/off outputs or by pulse width modulation.

If Oventrop actuators are used for room temperature control, a time-controlled setback of the room temperature via room thermostats is possible, for example by means of time programmes of the ClimaCon F room thermostats (e.g. ClimaCon F 210 / F 310).  

Oventrop offers actuators in “normally closed” or “normally open” versions. In the “normally closed” version, the valve is opened evenly when voltage is applied; this can be seen from the extended stroke indicator. If no voltage is applied to the actuator, the valve closes evenly after the idle time has elapsed.  The function of the thermal actuators “normally open” is reversed, when voltage is applied the valve is closed, in the de-energized state the valve is open.

Features

  • Simple plug-in mounting on valve adapter
  • Can be used in conjunction with room thermostats
  • Silent operation with low power consumption
  • Universally applicable
  • Mounting independent of position
  • Protected against overvoltage

Specifications

  • Make : Oventrop
  • Model: 1012450
  • Type: Normally Closed
  • Cable: 1M
  • Connection thread: M 30 x 1.5
  • Operating voltage: 24 V AC
  • Control Signal – 0-10V  
  • Switch-on current: < 320 mA for max. 100 ms
  • Continuous current:  42 mA
  • Stroke: 5 mm
  • Positioning force: > 90 N
  • Auxiliary switch, switching current:  5 A resistive load 1 A inductive load Protection type: IP 54 in all installation positions
  • Protection class: II according to EN 60730
  • Colour: RAL 9016 (traffic white)
  • Medium temperature: 0...+100 °C
  • Ambient temperature: 0…+60 °C
  • Storage temperature: -25…+60 °C

Contacts and Delivery

Fieldinstruments.lk
50/3, Angampitiya Rd, Ethul Kotte, Sri Lanka. 10100.
Phone: +94718555888 Email: info@fieldinstruments.lk