Protec - Protec 6000PLUS/OPHT/TSVAD Optical Smoke & Heat Sensor Plus Talking Sounder & Visual Alarm Device

Protec


Protec 6000PLUS/OPHT/TSVAD Optical Smoke & Heat Sensor Plus Talking Sounder & Visual Alarm Device - 6000PLUS/OPHT/TSVAD

Product Protec 6000PLUS/OPHT/TSVAD Optical Smoke & Heat Sensor Plus Talking Sounder & Visual Alarm Device
Brand Protec
Product Price 0 LKR
Datasheet Download

Description

General

The Protec Algo-Tec™ 6000PLUS sensor range has been developed to incorporate advanced fire sensing technology, electronic sounders, high intensity LED visual alarm devices (VAD) and speech enhanced talking sounder capability, all integrated within the sensor head and powered from the loop.

6000PLUS/OPHT/TSVAD Interactive addressable high performance optical smoke and heat multi-sensor.

The dual technology multi-criteria fire detector uses detection of smoke by scattering of infra-red within the optical chamber coupled with thermal enhancement of the optical sensitivity, as well as providing temperature detection equivalent to grade A2. The smoke and heat channels can be controlled independently for day/night operation with intelligent data being evaluated by the Protec Algo-Tec™ 6000PLUS interactive programmable algorithms.

These sensors react across the range of fire products from large visible particles from smouldering fires to open flaming fires producing very hot smaller particles and are therefore suitable for use in all smoke detection applications. The environmental conditioning algorithms can be selected to filter unwanted alarms and enhance performance.

Sensor Talking Sounder – For the ultimate method of alerting building occupants of the incidence of an emergency, the Protec Algo-Tec™ 6000PLUS sensor is equipped with an integrated voice enhanced sounder. The talking sounder is capable of delivering synchronised alert and evacuate messages around a building, removing any ambiguity, particularly for anyone unfamiliar with the building alert and evacuation strategy, enabling a more prompt and safe building evacuation.

Sensor VAD – Compliance with DDA legislation is assisted by the addition of the Protec visual alarm device (VAD) to the 6000PLUSensor, to warn those with hearing impairments or in noisy environments. The VAD utilises a high intensity LED with lower power consumption and increased reliability when compared to alternative indicators. The VAD is located in the centre of the sensor, so can be viewed from all angles. Suitable for ceiling mounting the VAD distributes light in a cylindrical pattern to achieve the required minimum illumination of 0.4lux over the entire coverage area in accordance with EN54-23. The maximum mounting height is 3m with a coverage diameter of 7.5m. For smaller areas the device can be programmed on-site for coverage diameter of 3m or 5m at reduced power.

Features

  • Dual Technology Sensor
  • Combined Smoke and Heat Sensor
  • Integrated Voice Enhanced Sounder
  • Integrated EN54-23 Visual Alarm Device
  • Seven Selectable Voice Messages
  • Loop Powered
  • Low Current
  • Programmable Volume Control
  • Integral Short Circuit Isolator
  • Protec Algo-Tec™ 6000PLUS Protocol
  • Devices Display Address Number
  • FAST™ Addressing
  • Reduced False Alarms
  • VAD Classification Adjustable from

3m to 7.5m Room Coverage Volume

Specifications

  • Make : protec
  • Model: 6000PLUS/OPHT/TSVAD
  • Environment  -10°C to +50°C (95% R.H. non condensing)
  • Ingress Protection    IP21C
  • Weight (excluding base)      111.38g
  • Loop Powered          Yes
  • Loop Voltage 18 – 28V
  • Loop Standby Load  0.55mA
  • Peak Alarm Load      25mA
  • Mounting Height      3m
  • Coverage       7.5m, 5m or 3m cylindrical diameter
  • VAD Flash Rate        1Hz or 0.5Hz white flash
  • Isolator         Yes
  • Device Protocol        Algo-Tec™ 6000PLUS
  • Dimensions (mm)    95ø x 54.5HDimensions (mm)      95ø x 54.5H