Description
General
Demand-based monitoring of differential pressures without auxiliary energy.
Features
- For monitoring the differential pressure in liquids, gases and vapours
- For use in, for example, filter technology and plant and machine engineering
- Differential pressure setting ranges from 0.06 to 6 bar
- Up to 80 °C media temperature
- High repeat precision
- High overload protection
- Can be used in all neutral media, such as heating water, neutral gases, oils etc.
- Long serviceable life
- With fitting bracket
Specifications
- Make: Sauter
- Model: DSD140F002
- Setting range (bar): 0.25...2.5
- Min. load: AC min: 0.1 A, 250 VAC, 25 VA DC min: 0.1 A, 30 VDC
- Max. load: AC max: 3(1) A, 250 VAC, 250 VA DC max: 0.4 A, 30 VDC, 10 W
- Temperature dependence: 1.5%/10 K Accuracy 3% of the setting range
- Hysteresis: 12% of the setting range
- Mechanical serviceable life: 10^6 switchings
- Max. static operating pressure (positive and negative pressure): 16 bar
- Ambient temperature: −10…70 °C
- Media temperature: 0...80 °C (non-freezing media)
- Ambient humidity: 45…75% rh
- Type of protection: IP65 (EN 60529)
- Protection class: II (EN 60730)
Accessories
- 0300360005 Cutting ring fitting G⅛" to 6 mm pipe (2 pcs)
- 0300360006 Pneumatic fitting G⅛" to 6 mm hose (2 pcs)
- 0300360016 Throttle screws G⅛", G⅛" (2 pcs)
Contacts and Delivery