Description
General
For acquiring the differential pressures in HVAC plant.Suited for use with the following types of media:
- Neutral or slightly aggressive gases
- Neutral or slightly aggressive heating water and cold water (with or without additives,such as hydrazine or glycol)
Features
- Operating voltage AC 24 V or DC 18...33 V
- Output signal DC 0...10 V
- Connecting male thread G½"
- 3 Versions covering a total differential pressure range of 0…10 bar
- Ceramics measurement system
- High level of safety against overpressures
Specifications
- Make: Siemens
- Model: QBE61.3-DP2
- Operating voltage: AC 24 V, DC 18...33 V
- Analog output, signal: DC 0...10 V
- Sensing element: Pressure diaphragm
- Pressure connection: External thread G ½ "
- Connection, electrical: Screw-free terminals
- Connecting thread: G ½"
- Medium temperature: -15…80 °C
- Max. permissible pressure: 20 bar
- PN class: PN 40
- Max. overpressure: -20…20 bar
- Mounting position: Any
- Measuring range, pressure: 0…5 bar
- Degree of protection: IP54
- Dimensions (W x H x D): 126 x 135 x 60 mm
Contacts and Delivery