Flame Detectors

Siemens QRA10.C UV Flame Detector – Normal Sensitivity with Aluminium Housing and IP54 Protection

Available to order MODEL QRA10.C

General The Siemens QRA10.C is a normal-sensitivity ultraviolet (UV) flame detector designed for monitoring gas flames and yellow- or blue-burning oil flames in industrial burner systems. It can also be used for ignition spark proving.

Supplied by FieldInstruments.lk Sri Lanka office · global sourcing network
Delivery time Confirmed with your quotation, based on availability
Freight & applicable duties Extra. Final costs will be provided with your quotation.
Need delivery to another country? Contact us for availability and delivery options.
Contact us

General
The Siemens QRA10.C is a normal-sensitivity ultraviolet (UV) flame detector designed for monitoring gas flames and yellow- or blue-burning oil flames in industrial burner systems. It can also be used for ignition spark proving.

The detector features a robust die-cast aluminium housing with a 1-inch mounting coupling and a connection facility for cooling air. Its bayonet fitting allows installation directly onto the mounting coupling or an AGG06 glass holder. The mounting coupling can be connected to a viewing tube or an AGG07 ball head.

Features
- UV flame detection for gas and oil-fired burner applications
- Normal sensitivity
- Suitable for yellow- and blue-burning oil flames
- Supports ignition spark proving
- Die-cast aluminium housing
- 1-inch mounting coupling
- Cooling air connection facility
- Bayonet mounting arrangement for flexible installation
- Suitable for direct burner mounting
- IP54 protection, upgradeable to IP65 with the AGG08 accessory
- Designed for intermittent burner operation
- Compatible with selected Siemens burner controls

Key Specifications
- Brand: Siemens
- Model: QRA10.C
- Article Number: BPZ:QRA10.C
- Product Type: UV Flame Detector
- Detection Principle: Ultraviolet radiation
- Sensitivity: Normal
- UV Response Range: 190–270 nm
- Operating Mode: Intermittent
- Housing Material: Die-cast aluminium
- Mounting Connection: 1-inch mounting coupling
- Mounting Arrangement: Bayonet fitting
- Cooling: Cooling air connection facility
- Safety Class: Class I
- Protection Rating: IP54 (IP65 with AGG08)
- Operating Temperature: -20 to +60 °C
- Maximum Combustion Chamber Pressure: 50 mbar (500 mbar with AGG03 or AGG02)
- Average UV Cell Life: Approximately 10,000 hours at a maximum ambient temperature of 50 °C
- Weight: Approximately 740 g
- Recommended Cable: H05VV-F 3 × 0.75 mm² (customer supplied)
- Spare UV Cell: AGR 4 502 1131 0
- Optional Accessories: AGG02 heat insulation glass, AGG03 quartz-glass lens, AGG06 glass holder, AGG07 ball head and AGG08 IP65 kit