General The Siemens QRA2 is a normal-sensitivity ultraviolet (UV) flame detector designed for flame supervision in gas and oil-fired burner systems. It detects UV radiation emitted by gas flames and yellow- or blue-burning oil flames, generating a flame signal for the compatible...
General
The Siemens QRA2 is a normal-sensitivity ultraviolet (UV) flame detector designed for flame supervision in gas and oil-fired burner systems. It detects UV radiation emitted by gas flames and yellow- or blue-burning oil flames, generating a flame signal for the compatible burner control system. It can also be used for ignition spark proving.
The QRA2 uses a UV-sensitive cell that responds to radiation in the 190–270 nm wavelength range. It is designed for intermittent burner operation and is compatible with selected Siemens burner controls.
Features
- UV flame detection technology for reliable burner flame supervision
- Normal sensitivity UV detector
- Suitable for gas flames and yellow- or blue-burning oil flames
- Supports ignition spark proving
- UV-sensitive cell operates in the 190–270 nm wavelength range
- Plastic housing with a metalized surface to prevent static charging caused by airflow
- Designed for direct mounting on the burner
- Does not respond to daylight, boiler-room illumination or glowing firebrick
- Compatible with selected Siemens burner controls, subject to the required interface or adapter
- Optional mounting flange and clamp configurations are available
Key Specifications
- Brand: Siemens
- Model: QRA2
- Product Type: UV Flame Detector
- Detection Principle: Ultraviolet (UV) radiation
- Sensitivity: Normal
- UV Response Range: 190–270 nm
- Operating Mode: Intermittent
- Safety Class: Class II
- Protection Rating: IP20; IP40 when fitted with suitable cable entries, such as the AGG09 kit
- Operating Temperature: -20 to +60 °C
- Humidity: Less than 95% RH
- Average UV Cell Life: Approximately 10,000 hours at a maximum ambient temperature of 50 °C
- Weight: Approximately 46 g
- Cable: Supplied by the customer; recommended cable H05VV-F 2 × 0.75 mm²
- Spare UV Cell: AGR 4 502 1131 0
Compatible Siemens Burner Controls: LGB2/LGB4 with AGQ1, LFL, LFE1, LFE10, LFS1.2, selected LME series with the required adapter, LMV2/LMV3 and LMV5 with AGQ1.
Important: The detector cable must be routed separately from other cables, especially high-voltage ignition cables. Confirm compatibility with the burner control and its required adapter before installation.
FieldInstruments.lk
International Inquiries:
Xelexon International (Pvt) Ltd
510, Level 05, Jana Jaya City, Rajagiriya, Sri Lanka 10100
Local Inquiries:
Nexus Engineering Solutions Pvt Ltd
237, Raja Maha Vihara Rd, Mirihana, Pitakotte, Sri Lanka 10100
Testing & Measuring Instruments:
Instrumentation Solutions (Pvt) Ltd
510, Level 05, Jana Jaya City, Rajagiriya, Sri Lanka 10100
Delivery time, freight and applicable duties are confirmed with your quotation.