General
The Siemens QRA2(2) is a normal-sensitivity ultraviolet (UV) flame detector designed for monitoring gas flames and yellow- or blue-burning oil flames in industrial burner systems. It can also be used for ignition spark proving.

The detector uses a UV-sensitive cell to detect ultraviolet radiation emitted by the flame and provides a flame signal to a compatible Siemens burner control. The QRA2(2) version is supplied with a straight mounting flange and clamp for burner installation.

Features
- UV flame detection technology
- Normal sensitivity
- Suitable for gas and oil flame supervision
- Supports ignition spark proving
- Detects UV radiation in the 190–270 nm range
- Straight mounting flange supplied
- Mounting clamp supplied
- Black terminal cover
- Metalized plastic housing to help prevent static charging caused by airflow
- Designed for direct burner mounting
- Compatible with selected Siemens burner controls

Key Specifications
- Brand: Siemens
- Model: QRA2(2)
- Article Number: BPZ:QRA2(2)
- Product Type: UV Flame Detector
- Detection Principle: Ultraviolet radiation
- Sensitivity: Normal
- UV Response Range: 190–270 nm
- Operating Mode: Intermittent
- Mounting: Straight flange and clamp
- Flange Part Number: 4 241 8898 0
- Clamp Part Number: 4 199 8806 0
- Terminal Cover: Black
- Safety Class: Class II
- Protection Rating: IP20; IP40 with suitable cable entry accessories
- Operating Temperature: -20 to +60 °C
- Humidity: Less than 95% RH
- Average UV Cell Life: Approximately 10,000 hours at a maximum ambient temperature of 50 °C
- Weight: Approximately 46 g
- Recommended Cable: H05VV-F 2 × 0.75 mm² (customer supplied)
- Spare UV Cell: AGR 4 502 1131 0