System Sensor - System Sensor WFDTNRN Waterflow Detector

System Sensor


System Sensor WFDTNRN Waterflow Detector - WFDTNRN

Product System Sensor WFDTNRN Waterflow Detector
Brand System Sensor
Product Price 0 LKR
Datasheet Download

Description

General

The new WFDTN Series waterflow detectors from System Sensor consists of a rugged, NEMA 4-rated enclosure that is more damage resistant than previous metal designs. The waterflow detector is designed for both indoor and outdoor use, with the widest available temperature range, from 32°F to 150°F.

Both the WFDTN with incorporated timer and WFDTNRN with immediate activation fit any tee that has a 1 in. NPT branch, including: 1in., 1¼in., 1½ in. and 2in. NPT threaded ferrous and brass tees; 1in., 1¼in., 1½in. and 2in. copper sweat tees; Tyco, Spears, NIBBCO brand 1 in. CPVC tees. Twelve different clearly marked plastic paddles are available to fit different installation configurations.

UL-listed models are equipped with tamper-resistant cover screws to prevent unauthorized entry. Inside, two sets of SPDT (Form C) synchronized switches are enclosed in a durable terminal block with new layout designed to make wiring easy with wire ready terminals, COM terminals are on a different elevation, large barrier between switches and easy to read raised textured lettering all make wiring easy. An optional cover tamper switch is available, securely snaps into place, no tools required.

The WFDTN incorporates a mechanical time delay feature, which minimizes the risk of false alarm due to pressure surges or air trapped in the fire sprinkler system. The larger and easy to turn timer dial makes setting the waterflow detector easy with high contrast pad printed markings. The dial offers three tabs to help with turning, with one larger tab located on the dial position for approximately 60 seconds, a notch is also indicated on the dial to locate approximately 30 seconds making setting the detector in dimmly lit locations easy.

The WFDTN series is designed for accuracy and repeatability. The detector also offers improved performance during vibration in riser applications where detectors are exposed to a large in rush of water.

Features:

  • New directional cover allows installers and inspectors to easily see the direction of flow
  • UL-listed models are NEMA 4 rated
  • New cover provides a better seal, is lighter weight, not painted and corrosion resistant
  • Sealed retard mechanism immune to dust and other contaminants
  • Less exposed metal reduces shock hazard, plastic cover acts as insulator and is resistant to arcing
  • Visual switch activation
  • Audible switch activation (73 dBA)
  • Field-replaceable timer/switch assembly
  • Accommodates up to 12 AWG wire
  • Switch Synchronization activates both alarm panel and local bell or horn strobe
  • Tamper-resistant cover screws
  • Improved water sealing
  • Reduced product weight
  • Wire-ready terminals
  • Improved wiring with new terminal block layout
  • Snap-in optional cover tamper switch

Specifications

  • Make : System Sensor  
  • Model: WFDTNRN
  • Static Pressure Rating: 375 PSI
  • Operating Temperature Range: 32°F to 150°F (0°C to 60°C)
  • Maximum Surge: 18 Feet Per Second (FPS)
  • Enclosure Rating: NEMA 4 – suitable for indoor/outdoor use
  • Triggering Threshold /Bandwidth (Flow Rate): 4–10 GPM
  • Cover Tamper Switch: Standard with ULC models, optional for UL models, part no. CTS
  • Conduit Entrances: Two openings for ½in. conduit. NEMA 4 rated plugs
  • Service Use: Automatic Sprinkler: NFPA-13, One or Two Family Dwelling: NFPA 13D, Residential Occupancies up to 4 Stories:, NFPA 13R National Fire Alarm Code: NFPA-72
  • Contact Ratings: Two sets of SPDT (Form C), 10.0 A, ½ HP @ 125/250 VAC, 2.5 A @ 6/12/24 VDC

Contacts and Delivery

Fieldinstruments.lk
50/3, Angampitiya Rd, Ethul Kotte, Sri Lanka. 10100.
Phone: +94718555888 Email: info@fieldinstruments.lk