Space/ Wall mount Temperature Sensors

Trend TR40-C-D1 Room Sensors and Display

Available to order MODEL TR40-C-D1

The TR40 and TR42 series of room sensors and displays are designed to operate with Trend IQX controllers. All models have an integral temperature sensor and variants are available that also include sensors for relative humidity and/or CO2 concentration.

Supplied by FieldInstruments.lk Sri Lanka office · global sourcing network
Delivery time Confirmed with your quotation, based on availability
Freight & applicable duties Extra. Final costs will be provided with your quotation.
Need delivery to another country? Contact us for availability and delivery options.
Contact us

General

The TR40 and TR42 series of room sensors and displays are designed to operate with Trend IQX controllers. All models have an integral temperature sensor and variants are available that also include sensors for relative humidity and/or CO2 concentration.

The TR42 features a monochrome backlit LCD display which can be configured to show sensor readings and allow user control of fan speed, occupancy and temperature setpoint. Up to 7 devices can be connected to the controller by a two wire Sylk™ bus which carries both data and power.

Features

  • Single power/data connection to controller reduces wiring.
  • Temperature sensing plus versions with humidity and/or CO2
  • Operates in either °C or °F.
  • Common backplate and connections allows easy upgrade from TR40 to TR42.

Specifications

  • Make : Trend
  • Model: TR40-C-D1
  • Dimensions (WxHxD) 84 x 121 x 21 mm (3.30 x 4.76 x 0.83”)
  • Material Main module:  ABS, Polylac PA-765, UV Stabilised Back plate ABS
  • Colour: White
  • Weight 0.103kg (0.23 lbs)
  • Protection: IP30
  • Connections: 2 part connector with 2 screw terminals for 0.33 to 0.82 mm2 (22 to 18 AWG) cross section area cable.
  • Temperature Sensor (all variants)
    • Range 0 to 52°C (32 to 125°F)
    • Accuracy ±0.2°C at 25°C (±0.36 °F at 77°F)
  • CO2 Concentration Sensor (-C-D1, -HC-D1 variants only)
    • Range 0 to 2000 ppm  (TR42 can display up to 9999 ppm)
    • Accuracy ±(30 ppm + 3% of measured value).