General
The high performance differential pressure transmitter EJX110A features single crystal silicon resonant sensor and is suitable to measure liquid, gas, or steam fl ow as well as liquid level, density and pressure. EJX110A outputs a 4 to 20 mA DC signal corresponding to the measured differential pressure. Its highly accurate and stable sensor can also measure the static pressure which can be shown on the integral indicator or remotely monitored via BRAIN or HART communications. Other key features include quick response, remote set-up using communications, diagnostics and optional status output for pressure high/low alarm. The multi-sensing technology provides the advanced diagnostic function to detect such abnormalities as an impulse line blockage or heat trace breakage. FOUNDATION Fieldbus and PROFIBUS PA protocol types are also available. All EJX series models in their standard configuration, with the exception of the Fieldbus and PROFIBUS types, are certified as complying with SIL 2 for safety requirement.
Specifications
- Make: Yokogawa
- Model: EJX110A-EMS5G-917DJ/KF22/D4/X2/M01/T13/DG6/HC
- Product Type : Differential Pressure Transmitter
- Output signal : E = 4 to 20 mA DC with digital communication (HART 5 protocol)
- Measurement span (capsule) : M = 0.5 to 100 kPa (2 to 400 inH2O)
- Wetted parts material : S = Cover flange and process connector ASTM CF-8M *1, Capsule Hastelloy C-276 *2 (Diaphragm)F316L SST, 316L SST (Others), Capsule gasket Teflon-coated 316L SST, Vent/Drain plug 316 SST
- Process connections : 5 = without process connector (1/4 NPT female on the cover flanges)
- Bolts and nuts material : G = 316L SST
- Installation : 9 = Horizontal piping and left side high pressure
- Amplifier housing : 1 = Cast aluminum alloy
- Electrical connection : 7 = 1/2 NPT female, two electrical connections and a blind plug
- Integral indicator : D = Digital indicator
- Mounting bracket : J = 316 SST 2-inch pipe mounting, flat type (for horizontal piping)
- ATEX : KF22 = ATEX Flameproof Approval *1 Applicable Standard: EN 60079-0:2012+A11:2013, EN 60079-1:2014, EN 60079-31:2014 Certificate: KEMA 07ATEX0109 X II 2G, 2D Ex d IIC T6...T4 Gb (“Ex db IIC T6...T4 Gb” from August 1, 2017), Ex tb IIIC T85°C Db Degree of protection: IP66/IP67 Amb. Temp. (Tamb) for gas-proof : T4; –50 to 75°C (–58 to 167°F), T5; –50 to 80°C (–58 to 176°F), T6; –50 to 75°C (–58 to 167°F) Process Temp. for gas-proof (Tp): T4; –50 to 120°C (–58 to 248°F), T5; –50 to 100°C (–58 to 212°F), T6; –50 to 85°C (–58 to 185°F) Max. surface Temp. for dust-proof: T85°C (Tamb: –30 to 75°C, Tp: –30 to 85°C) *3
- Calibration units : D4 = M calibration (kgf/cm2 unit)
- Painting : X2 = Coating change, Anti-corrosion coating
- Material certificate : M01 = Cover flange
- Pressure test/ Leak test certificate : T13 = Test Pressure: 25 MPa(3600 psi), Nitrogen(N2) Gas*20 Retention time: one minute
- Advanced diagnostics* : DG6 = Multi-sensing process monitoring • Impulse line blockage detection *22 • Heat trace monitoring
- 316 SST exterior parts : HC = 316 SST zero-adjustment screw and setscrews