General
The microprocessor based control OBC 82.12 offers stable and precise timings independent of variations in supply voltage and ambient temperature. The control is undervoltage protected. In case of undervoltage the control will prevent the burner from starting and simultaneously show a flash code. Besides this, up to five other fault types can be read out as flash codes when the control is in lockout. The design complies with the requirements of the RoHS and WEEE directive.
Features
- For 2 stage burners up to 30 kg/h
- For burners with or without preheater
- Precise and reproducible timings
- Limitation at 3 restarts by flame failure within the same operating period
- Limitation of 10 min. on preheating time
- Remote alarm output
- Indication of reason for lockout
- Indication of preheating and operation
Specifications
- Make: Danfoss
- Model: OBC 82.12
- Order Code: 057H8716
- Rated voltage: 230 V~
- Operating range: 195-253 V~
- Frequency: 50-60 Hz ± 6%
- Consumption: 6 VA
- Reset: Immediately
- Reaction time on flame failure: Max. 1 s
- Undervoltage protection: < 170 V
- Protection class: II
- Pollution degree: 2
- Main fuse (terminal load, see electrial diagram) : Max. 10 A
- Cable connection: Plate for 5 PG 11 screwed connections or plate with knockouts
- Ambient temperature:-20 to +60°C
- Installation: Any position
- Enclosure: IP40
- Flame monitoring: UV, LD or LDS
- Required flame signal: No flame / dark ≤5 μA Flame / light ≥65 μA
- Max. cable length between OBC and UV, LD/LDS: 20 m (installed separately)