Delta - Delta Application Controller 3 universal inputs, 2 binary outputs, 2 analog outputs

Delta


Delta Application Controller 3 universal inputs, 2 binary outputs, 2 analog outputs - DAC-322

Product Delta Application Controller 3 universal inputs, 2 binary outputs, 2 analog outputs
Brand Delta
Product Price 0 LKR
Datasheet Download

Description

General

The DAC-322 is a fully programmable, Native BACnet® Advanced Application Controller that communicates on an RS-485 LAN using the BACnet MS/TP protocol. This controller is designed for a wide-range of applications that have small local I/O requirements. It also supports BACstat® and other Delta LINKnet devices.

Features

  • Fully programmable in GCL+
  • Supports 4 BACstat network sensors on LINKnet for room sensing and control or 2 Delta Field Modules on LINKnet for I/O expansion
  • Actuator power terminal (24 VAC) for each analog output (can be powered internally or from an auxiliary transformer)
  • Firmware upgrade and database load/ save over the network
  • Supports Modbus capability via flash loading in the fieldService port
  • Screw or DIN rail mountable
  • LED indicator for each output, power, CPU and SCAN status

Specifications

  • Make: Delta
  • Model: DAC-304
  • BACnet Device Profile: BACnet Advanced Application Controller (B-AAC)
  • Inputs: 3 Universal Inputs (10-bit) supporting:
      • 0-5 VDC
      • 0-10 VDC
      • 10 kΩ Thermistor
      • Dry Contact (using 10 kΩ Thermistor
      • jumper setting)
      • 4-20 mA
  • Outputs:
      • 2 Binary TRIAC Outputs (jumper configured for internal or external power)
      • 2 Analog outputs (0-10 VDC), software configurable as binary or analog
  • Connectors: Removable screw-type terminal connectors
  • Wiring Class: Class 2 / SELV
  • Power: 24 VAC 50/60 Hz @ 8 VA, 80 VA with fully-loaded TRIAC Outputs
  • Technology:
      • 16-bit processor
      • 1 MB Flash memory
      • 127 KB SRAM memory for database
  • Communications Ports;
      • Main LAN (NET1) BACnet MS/TP @ 9600, 19200, 38400 or 76800 bps (default), max of 99 devices per BACnet MS/TP network
      • SubLAN (NET2) Delta LINKnet @ 76800 bps, max 4 devices on LINKnet, with no more than 2 DFM devices

Contacts and Delivery

Fieldinstruments.lk
50/3, Angampitiya Rd, Ethul Kotte, Sri Lanka. 10100.
Phone: +94718555888 Email: info@fieldinstruments.lk