General
Description The IQ®41x Series Controllers have 5 inputs (3 universal, 2 digital) and 6 outputs. The IQ411 has 6 solid state digital outputs, and the IQ412 has 4 solid state digital outputs and 2 analogue voltage outputs. The IQ41x series uses Ethernet and TCP/IP networking technologies with embedded XML and is fully compatible with other Trend IQ controllers. Trend communications over a current loop LAN and support for BACnet over IP are available as options. A local PC or display (e.g. IQView4) can be connected to the RS232 port. A Wallbus port is also provided for use with room displays.
Features
- 11 onboard I/O channels - 5 inputs and 6 outputs
- Ethernet 10/100 Mbps main network with TCP/IP protocol
- Trend current loop LAN option
- Embedded XML Web Services as standard
- BACnet over IP option (certified as a BACnet Application Specific Controller)
- Wallbus for connection of room displays
- RS232 and USB local supervisor/engineering ports
- Automatic time synchronisation and daylight saving via SNTP
- DIN rail mounting, DIN 19 size 2 standard enclosure
- 230 Vac or 24 Vac input power supply options
- Features to replace IQ211, IQ212, and IQ7x Series controllers
- Retrofit mounting plate and cable extender accessories
Specifications
- Make: Trend
- Product code: IQ412-1000U500200
- Product order code: IQ412/INT/24VAC
- Controller type: Plant controllers
- Communication protocols: Bacnet | Wallbus
Electrical Data
- Power Input /230 :230 Vac ±10% 50/60 Hz at up to 40 VA /24VAC :24 Vac ±10% 50/60 Hz at up to 30 VA
- Fusing: No replaceable fuses required.
- Power Failure Protection Strategy & data :non-volatile flash memory.
Real time clock : supercap, maintained for up to 8 days (typical).
- Clock Accuracy: 10 s per month (typical).
- Cycle Time: Sequence table 1 s.
Ethernet Network
- Transmission :10/100 BASE-T (IEEE 802.3).
- Connection :RJ45, auto MDI-X.
- Cable Type: :Cat 5e, UTP (unshielded twisted pair).
- Distance (to hub) :100 m (109 yds) maximum
- Virtual CNCs :1.
- Address :Not set by default – set to desired value in range 1 to 119 (excluding 2, 3, & 10) using configuration mode. Address must be unique on LAN.
Universal Inputs
- Function :Measuring voltage, current, thermistor
- or digital input (function set by strategy).
- Input Noise Rejection: Minimum 60 dB series mode rejection at input power supply frequency.
- Input Resolution: 12 bit (4096 steps).
Voltage Input
- Input range: 0 to 10 V.
- Input resistance: 9.4 kΩ.
- Accuracy: ±0.5% of span (50 mV).
Current Input
- Input range: 0 to 20 mA.
- Input resistance: 120 Ω.
- Accuracy: ±0.5% of span (100 μA).
Thermistor Input
- Temperature (NTC 10 kΩ @ 25°C (77°F))
- Input range :-40 to 110°C (-40°F to 230°F)
- Accuracy :±0.3°C (-20°C to 90°C (-4°F to 194°F)); ±0.4°C (<-20°C (-4°F) or >90°C (194°F))
Resistance
- Input range :0 to 200 kΩ
- Accuracy: 1% of measured value or 10 Ω, whichever is the greater.
- Bridge resistor: 12.2 kΩ.
- Bridge supply: 3.3 V.
Digital Input
- Input voltage: 0 to 5 Vdc typical (50 Vdc maximum).
- ON state :< 2.5 V @ 270 μA (sink).
- OFF state :> 3.5 V (or open circuit).
- Count rate: 30 Hz max. (pulse width ≥16.6 ms).