General
The DAC-606 is a fully programmable, Native BACnet® Advanced Application Controller that either communicates on Twisted-Pair Ethernet 10-BaseT using BACnet IP and BACnet over Ethernet (DAC-606E) or an RS-485 LAN using the BACnet MS/TP protocol (DAC-606). It is designed for a wide-range of applications that have small local I/O requirements. It also supports BACstat® network sensors and other Delta LINKnet devices.
Features
- Native BACnet firmware
- Fully programmable in GCL+
- Maintenance free super capacitor for real-time clock and SRAM backup on DAC-606E
- Supports 6 BACstat network sensors on LINKnet for room sensing and control or 2 Delta Field Modules on LINKnet for I/O expansion
- Firmware upgrade and database load/ save over the network
- Supports Modbus® capability via flash loading in the field
- Service port
- Screw or DIN rail mountable LED indicator for each output, power, CPU and SCAN status
Specifications
- Make: Delta
- Model: DAC-606E
- BACnet Device Profile: BACnet Advanced Application Controller (B-AAC)
- Inputs: 11 Universal Inputs (10-bit) supporting:
-
- 0-5 VDC
- 0-10 VDC
- 10 kΩ Thermistor
- Dry Contact (using 10 kΩ Thermistor
- jumper setting)
- 4-20 mA
- Outputs:
-
- 6 Binary TRIAC Outputs (jumper configured for internal or external power)
- Device Addressing: Set via DIP switches and jumpers, or software setup
- Connectors: Removable screw-type terminal connectors
- Wiring Class: Class 2 / SELV
- Power: 24 VAC 50/60 Hz @ 8 VA, 80 VA with fully-loaded TRIAC Outputs
- Technology:
- (non-Ethernet version) 16-bit processor 1 MB Flash memory 127 KB SRAM memory for database
- (Ethernet version) 16-bit processor 2 MB Flash memory 319 KB SRAM memory for database Super Capacitor for 72-hour backup of real-time clock and SRAM
- Communications Ports;
-
- Twisted-Pair Ethernet (10-BaseT) @ 10 MB, BACnet IP, BACnet over Ethernet
- Main LAN (NET1): BACnet MS/TP @ 9600, 19200, 38400 or 76800 bps (default), max of 99 devices per BACnet MS/TP network
- SubLAN (NET2): Delta LINKnet @ 76800 bps, max 6 devices on LINKnet, with no more than 2 DFM devices