General The DUNGS VPS 504 S01 is an automatic valve proving system designed to check the tightness of gas safety shut-off valves before burner operation. It verifies the sealed condition of the valve section between two valves by using an integrated motor pump to increase the tes...
General
The DUNGS VPS 504 S01 is an automatic valve proving system designed to check the tightness of gas safety shut-off valves before burner operation. It verifies the sealed condition of the valve section between two valves by using an integrated motor pump to increase the test pressure and a differential pressure switch to monitor pressure changes.
Designed for use with DUNGS single valves, DMV double solenoid valves and GasMultiBloc systems, the VPS 504 complies with EN 1643. It provides a visual indication of successful testing or leakage through its LED indicators and releases the burner control when the test is completed successfully.
Features
- Automatic gas valve tightness testing
- Designed for multiple actuator systems
- Complies with EN 1643
- Integrated motor pump for pressure build-up
- Differential pressure monitoring
- LED indication for tightness and leakage
- Short test period of approximately 10 to 36 seconds
- No on-site adjustment required
- 7-pole plug connection
- Electrical connection according to DIN 4791
- Optional group fault alarm (SSM) for S01
- Suitable for DUNGS single valves, DMV double solenoid valves and GasMultiBloc systems
- Suitable for natural gas, LPG within the specified gas composition limits, biogas and other compatible gaseous media
Key Specifications
- Brand: DUNGS
- Model: VPS 504 S01
- Product Type: Automatic Valve Proving System
- Function: Gas valve tightness testing
- Applicable Standard: EN 1643
- Maximum Operating Pressure: 500 mbar (50 kPa)
- Test Volume: 0.1 to 4.0 litres
- Pressure Increase by Motor Pump: Approximately 20 mbar
- Test / Release Time: Approximately 10 to 36 seconds
- Sensitivity Limit: Maximum 50 l/h
- Power Consumption: Approximately 60 VA during pumping; 17 VA during operation
- Switching Current – Operating Output: Maximum 4 A
- Degree of Protection: IP40
- Ambient Temperature: -15 to +70°C for 230 VAC, 50 Hz; -15 to +60°C for other versions
- Duty Cycle: 100%
- Maximum Test Cycles: 20 per hour
- Electrical Connection: 7-pole plug connection
- Wiring Standard: DIN 4791
- Cable Length: Available in different lengths; 2 m version listed under order number 219876
- Installation Position: Vertical or horizontal; not upside down
- Compatible Media: Gas families 1, 2 and 3, and other suitable gaseous media
- Optional Function: Group fault alarm (SSM)
FieldInstruments.lk
International Inquiries:
Xelexon International (Pvt) Ltd
510, Level 05, Jana Jaya City, Rajagiriya, Sri Lanka 10100
Local Inquiries:
Nexus Engineering Solutions Pvt Ltd
237, Raja Maha Vihara Rd, Mirihana, Pitakotte, Sri Lanka 10100
Testing & Measuring Instruments:
Instrumentation Solutions (Pvt) Ltd
510, Level 05, Jana Jaya City, Rajagiriya, Sri Lanka 10100
Delivery time, freight and applicable duties are confirmed with your quotation.