Burner Controllers

DUNGS VPS 504 S03 Automatic Gas Valve Proving System – 230 VAC, 50 Hz, 1.5 m Cable, IP40

Available to order MODEL VPS 504 S03

General The DUNGS VPS 504 S03 is an automatic valve proving system designed to verify the tightness of gas safety shut-off valves before burner operation. It checks the sealed section between two valves by using an integrated motor pump to build up test pressure and a differentia...

Supplied by FieldInstruments.lk Sri Lanka office · global sourcing network
Delivery time Confirmed with your quotation, based on availability
Freight & applicable duties Extra. Final costs will be provided with your quotation.
Need delivery to another country? Contact us for availability and delivery options.
Contact us

General
The DUNGS VPS 504 S03 is an automatic valve proving system designed to verify the tightness of gas safety shut-off valves before burner operation. It checks the sealed section between two valves by using an integrated motor pump to build up test pressure and a differential pressure switch to monitor pressure changes.

The S03 version features a 7-pole plug connection, wiring according to DIN 4791 and a 1.5 m cable. With IP40 enclosure protection, it is designed for use with compatible DUNGS single valves, DMV double solenoid valves and GasMultiBloc systems. The VPS 504 series complies with EN 1643.

Features
- Automatic gas valve tightness testing
- Designed for multiple actuator systems
- Complies with EN 1643
- Integrated motor pump for pressure build-up
- Differential pressure monitoring
- LED indication for tightness and leakage
- Test and release period of approximately 10 to 36 seconds
- No on-site adjustment required
- 7-pole plug connection
- DIN 4791 wiring configuration
- 1.5 m cable length
- IP40 enclosure protection
- Suitable for compatible DUNGS single valves, DMV double solenoid valves and GasMultiBloc systems

Key Specifications
- Brand: DUNGS
- Model: VPS 504 S03
- Order Number: 223590
- Product Type: Automatic Valve Proving System
- Function: Gas valve tightness testing
- Applicable Standard: EN 1643
- Supply Voltage: 230 VAC
- Frequency: 50 Hz
- Maximum Operating Pressure: 500 mbar (50 kPa)
- Test Volume: 0.1 to 4.0 litres
- Pressure Increase by Motor Pump: Approximately 20 mbar
- Test / Release Time: Approximately 10 to 36 seconds
- Sensitivity Limit: Maximum 50 l/h
- Power Consumption: Approximately 60 VA during pumping; 17 VA during operation
- Switching Current – Operating Output: Maximum 4 A
- Degree of Protection: IP40
- Ambient Temperature: -15 to +70°C
- Duty Cycle: 100%
- Maximum Test Cycles: 20 per hour
- Electrical Connection: 7-pole plug connection
- Wiring Standard: DIN 4791
- Cable Length: 1.5 m
- Installation Position: Vertical or horizontal; not upside down
- Compatible Media: Gas families 1, 2 and 3, and other suitable gaseous media