Burner Controllers

DUNGS VPS 504 S04 Automatic Gas Valve Proving System – Screw Terminal Connection, IP54, Floating Fault Signal

Available to order MODEL VPS 504 S04

General The DUNGS VPS 504 S04 is an automatic valve proving system designed to check the tightness of gas safety shut-off valves before burner operation. It uses an integrated motor pump to increase the pressure in the test section and a differential pressure switch to monitor pr...

Supplied by FieldInstruments.lk Sri Lanka office · global sourcing network
Delivery time Confirmed with your quotation, based on availability
Freight & applicable duties Extra. Final costs will be provided with your quotation.
Need delivery to another country? Contact us for availability and delivery options.
Contact us

General
The DUNGS VPS 504 S04 is an automatic valve proving system designed to check the tightness of gas safety shut-off valves before burner operation. It uses an integrated motor pump to increase the pressure in the test section and a differential pressure switch to monitor pressure changes and detect leakage.

The S04 version features screw-terminal electrical connections, a PG 13.5 cable entry with provision for PG 11, and a floating fault signal for remote monitoring. Its IP54 enclosure protection makes it suitable for industrial burner and gas train installations. The VPS 504 series complies with EN 1643.

Features
- Automatic gas valve tightness testing
- Designed for multiple actuator systems
- Complies with EN 1643
- Integrated motor pump for pressure build-up
- Differential pressure monitoring
- LED indication for tightness and leakage
- Test and release period of approximately 10 to 36 seconds
- No on-site adjustment required
- Screw-terminal electrical connections
- PG 13.5 cable entry; PG 11 also possible
- Floating fault signal for control-room monitoring
- IP54 enclosure protection
- Available in different voltage and frequency configurations
- LPG version available

Key Specifications
- Brand: DUNGS
- Model: VPS 504 S04
- Product Type: Automatic Valve Proving System
- Function: Gas valve tightness testing
- Applicable Standard: EN 1643
- Maximum Operating Pressure: 500 mbar (50 kPa)
- Test Volume: 0.1 to 4.0 litres
- Pressure Increase by Motor Pump: Approximately 20 mbar
- Test / Release Time: Approximately 10 to 36 seconds
- Sensitivity Limit: Maximum 50 l/h
- Power Consumption: Approximately 60 VA during pumping; 17 VA during operation
- Switching Current – Operating Output: Maximum 4 A
- Switching Current – Interference Output: Maximum 1 A for applicable versions
- Degree of Protection: IP54
- Ambient Temperature: -15 to +70°C for 230 VAC, 50 Hz; -15 to +60°C for other versions
- Duty Cycle: 100%
- Maximum Test Cycles: 20 per hour
- Electrical Connection: Screw terminals
- Cable Entry: PG 13.5; PG 11 also possible
- Fault Signal: Floating relay output (NC, COM, NO)
- Installation Position: Vertical or horizontal; not upside down
- Compatible Media: Gas families 1, 2 and 3, and other suitable gaseous media
- Available Voltage Versions: 230 VAC, 50 Hz; 220 VAC, 60 Hz; 120 VAC, 60 Hz; 110 VAC, 50 Hz
- Standard 230 VAC Order Number: 219881
- LPG Version Order Number: 226316