Honeywell - Honeywell/Satronic TF836.3 Oil Burner Safety Control Box

Honeywell


Honeywell/Satronic TF836.3 Oil Burner Safety Control Box - TF 836.3

Product Honeywell/Satronic TF836.3 Oil Burner Safety Control Box
Brand Honeywell
Product Price 0 LKR
Datasheet Download

Description

General

Honeywell/ Satronic TF 834.3 / 836.3 for 1- or 2-stage oil power burners up to 30kg/ h capacity with or without oil preheater and intermittent operations. Flame detection:

  • Photoresistor MZ 770 S
  • Infrared-flicker detector IRD 1010
  • UV solid state sensor UVD 970.

Features:

  • The control box circuitry is protected by a flame resistant, transparent plastic housing. It incorporates the thermomechanical, temperature compensated timer, and flame check and reset circuits. Manual reset from lockout is provided by a push button with an integrated lockout signal lamp.
  •  A central fixing screw locks the control box to the wiring base. The wiring base and control box have a positive plug-in arrangement, making it impossible to achieve an incorrect connection between the two parts. A variety of cable entry points provides utmost flexibility of electrical wiring.
  • The TF 834 and TF 834 E are fully compatible with the TF 734 and TF 734-2 respectively.
  • Using the TF 83X.3 as a replacement, the flame detector IRD 911 must be replaced by its compatible type IRD 1010. An optional extension button (item no. 70601) compensates for height differences.

Specifications

  • Make : Honeywell / Satronic
  • Model: TF 836.3
  • Operating voltage: 220/240 V (-15..+10%) 50 Hz (40-60Hz)
  • Fuse rating: 10 A fast, 6 A slow
  • Power consumption: ca. 5 VA
  • Max. load per output
      • - terminal 31.5 A, cos ϕ 0.2
      • - terminal 44.0 A, cos ϕ 0.4
      • - terminal 50.5 A, cos ϕ 0.4
      • - terminal 64.0 A, cos ϕ 0.4
      • - terminal 70.1 A, cos ϕ 0.4
      • - terminal B0.5 A, cos ϕ 0.4 total load5.0 A, cos ϕ 0.4 Pre
      • -purge timeca. 12 sec. Pre
      • -ignition timeca. 12 sec.
  • Delay time to oil valve:  2ca. 20 sec. (TF 836.3)
  • Lockout safety time: 10 sec.
  • Flame detector: MZ 770 Sside-on and end-on viewing Light sensitivity MZ 770 S> 6 Lux IRD 1010side-on or end-on viewing UVD 970end-on viewing

Contacts and Delivery

Fieldinstruments.lk
50/3, Angampitiya Rd, Ethul Kotte, Sri Lanka. 10100.
Phone: +94718555888 Email: info@fieldinstruments.lk