Jonson Controls - Jonson Controls Direct Mount Pressure-Actuated Condenser Fan Speed Controllers for Single-Phase Motors

Johnson Controls is a world leader in smart buildings, creating safe, healthy and sustainable spaces.


Jonson Controls Direct Mount Pressure-Actuated Condenser Fan Speed Controllers for Single-Phase Motors - P215PR-9203

Product Jonson Controls Direct Mount Pressure-Actuated Condenser Fan Speed Controllers for Single-Phase Motors
Brand Jonson Controls
Product Price 0 LKR
Datasheet Download

Description

General

The Series P215PR/RM direct-mount and remote- mount pressure-actuated condenser fan speed controllers are designed for speed variation of single-phase motors. Head pressure control of a refrigeration system, through speed variation of the fan on an air-cooled condenser, results in optimum performance throughout the year. Once the output drops below 30%, the fan is cut off. The Series P215PR/RM controllers are designed for non-corrosive refrigerant systems. See Table 1 for a list of features and benefits.

A pressure-actuated control provides the most direct and fastest response to pressure variations in the refrigerant system. The controller varies the supply voltage to the motor from 30% to at least 95% over the proportional band using the phase-cutting principle. This principle provides speed variation of a permanent split capacitor or shaded pole motors that do not draw more than 4 A (RMS) full-load current. The motor manufacturer should have approved the product for this speed control principle.  

We recommend confirming with the electric motor manufacturer that the motor can be used with a controller, using the phase-cutting principle for speed variation. You can also provide a copy of this product data sheet to the motor manufacturer or supplier for review.

Features

  • Fan Speed Variation Condenser Pressure Control
  • Pressure Input
  • Direct/Remote Mount Option
  • Setpoint Screw Location on Top of Device
  • Built-in Suppression Filter
  • IP65 Enclosure
  • Compact Design
  • Pressure Range 5-42 bar

Specifications

  • Make: Jonson Controls
  • Model: P215PR-9203
  • Range: 5 to 15 Bar
  • Setting: 9 Bar
  • Proportional Band: 3  Bar
  • Maximum Output Voltage: 95% of Supply Voltage
  • Maximum Current: 4 A RMS (at maximum voltage output)
  • Operating Ambient Temperature: -40° to 55°C
  • Minimum Current: 200 mA
  • Residual Current Motor: 25 mA
  • Power Factor (cos) Motor: 0.6
  • Main Supply Voltage: 230 VAC + 8% / -15%
  • Main Supply Frequency: 50/60 Hz
  • Cut-off Point: 30% of Supply Voltage
  • Enclosure: IP65

Contacts and Delivery

Fieldinstruments.lk
50/3, Angampitiya Rd, Ethul Kotte, Sri Lanka. 10100.
Phone: +94718555888 Email: info@fieldinstruments.lk