Earth ground testers

KYORITSU 2433R Leakage Clamp Meter – 400 A AC, 0.01 mA Resolution, Harmonic Filtering

Available to order MODEL 2433R

General The KYORITSU MODEL 2433R is a leakage clamp meter designed for measuring AC leakage current in electrical installations and equipment. It offers three measurement ranges: 40 mA, 400 mA and 400 A, with a minimum resolution of 0.01 mA for sensitive leakage current measureme...

Supplied by FieldInstruments.lk Sri Lanka office · global sourcing network
Delivery time Confirmed with your quotation, based on availability
Freight & applicable duties Extra. Final costs will be provided with your quotation.
Need delivery to another country? Contact us for availability and delivery options.
Contact us

General
The KYORITSU MODEL 2433R is a leakage clamp meter designed for measuring AC leakage current in electrical installations and equipment. It offers three measurement ranges: 40 mA, 400 mA and 400 A, with a minimum resolution of 0.01 mA for sensitive leakage current measurements.

The instrument features a frequency selector switch that helps eliminate the effects of harmonic components during measurement. With a maximum conductor diameter of 40 mm and a wide frequency response, the 2433R is suitable for electrical maintenance, leakage current investigation and inspection of industrial electrical systems.

Features
- Three AC current measurement ranges: 40 mA, 400 mA and 400 A
- Minimum resolution of 0.01 mA
- Frequency selector switch to reduce the influence of harmonic components
- Wide frequency response from 20 Hz to 1 kHz
- AC current measurement up to 400 A
- Maximum conductor diameter of 40 mm
- Compact and lightweight design
- Approximately 2-second response time
- Suitable for leakage current measurement and electrical maintenance

Key Specifications
- AC current measurement (50/60 Hz): 40 mA / 400 mA / 400 A
- Accuracy (40 mA / 400 mA ranges): ±1% of reading ±5 digits
- Accuracy (400 A range, 0–300 A): ±1% of reading ±5 digits
- Accuracy (400 A range, 300.1–399.9 A): ±2% of reading
- AC current measurement (WIDE): 40 mA / 400 mA / 400 A
- Wide-range accuracy (40 mA / 400 mA): ±2.5% of reading ±10 digits (20 Hz–1 kHz)
- Wide-range accuracy (400 A, 0–300 A): ±2.5% of reading ±10 digits (40 Hz–1 kHz)
- Wide-range accuracy (400 A, 300.1–399.9 A): ±5% of reading (40 Hz–1 kHz)
- Minimum resolution: 0.01 mA
- Maximum conductor diameter: 40 mm
- Frequency response: 20 Hz–1 kHz; 40 Hz–1 kHz on the 400 A range
- External stray magnetic field effect: Approximately 10 mA AC near a 15 mm conductor carrying 100 A AC
- Response time: Approximately 2 seconds
- Applicable standards: IEC 61010-1 CAT III 300 V, Pollution Degree 2; IEC 61010-2-032
- Power supply: 2 × R03 (1.5 V) batteries
- Dimensions: 185 × 81 × 40 mm
- Weight: Approximately 270 g (including batteries)