Emerson - Rosemount 248 Head-Mount Temperature Transmitter – HART 4–20 mA, DIN B

Emerson


Rosemount 248 Head-Mount Temperature Transmitter – HART 4–20 mA, DIN B - 248HANAN0Q4

Product Rosemount 248 Head-Mount Temperature Transmitter – HART 4–20 mA, DIN B
Brand Emerson
Product Price 0 LKR
Datasheet Download

Description

General
The Rosemount 248 (248HANAN0Q4) is a head-mount temperature transmitter designed for dependable temperature measurement in industrial process applications. It accepts a range of temperature sensor inputs, including RTDs, thermocouples, resistance and millivolt signals, and converts the measured value into a 4–20 mA analogue output with HART digital communication.

This configuration features a DIN B head-mount design, no enclosure and no hazardous-area certification. It also includes a Q4 three-point calibration certificate, providing documented calibration at 0%, 50% and 100% of the output range. The compact transmitter is suitable for installation inside compatible temperature connection heads.

Features
- HART communication with 4–20 mA analogue output
- DIN B head-mount transmitter design
- Universal input for RTDs, thermocouples, resistance and millivolt signals
- Single-sensor input capability
- Three-point calibration certificate included
- Calibration points at 0%, 50% and 100%
- Open- and short-sensor diagnostics
- Ambient operating temperature range of -40 to +85°C
- Suitable for installation in compatible temperature connection heads
- Compact transmitter design for industrial process monitoring

Key Specifications
- Brand: Rosemount
- Manufacturer: Emerson
- Model: 248
- Manufacturer Part Number: 248HANAN0Q4
- Product Type: Head-Mount Temperature Transmitter
- Transmitter Type: DIN B Head Mount
- Output Signal: 4–20 mA
- Communication Protocol: HART
- Sensor Input Types: RTD, Thermocouple, Resistance and Millivolt
- Sensor Configuration: Single Sensor
- Product Certification: NA – No Approval
- Enclosure Configuration: N – No Enclosure
- Conduit Entry: 0 – No Enclosure
- Calibration Option: Q4 – Three-Point Calibration Certificate
- Calibration Points: 0%, 50% and 100%
- Power Supply: 12.0–42.4 V DC at transmitter terminals
- Minimum Supply Voltage: 17.75 V DC with 250 Ω load
- Operating Temperature: -40 to +85°C
- Humidity Limit: 0–95% RH, non-condensing
- Damping: 5 seconds default; adjustable up to 32 seconds
- Update Rate: Less than 0.5 seconds
- Weight: Approximately 50 g
- Mounting: DIN B temperature connection head

Contacts and Delivery

FieldInstruments.lk
50/3, Angampitiya Rd, Ethul Kotte, Sri Lanka. 10100.
Phone: +94718555888
WhatsApp: +94 71 388 7888
Email: info@fieldinstruments.lk