General
LME are used for the startup and supervision of 1- or 2-stage gas burners or gas burners in intermittent operation. Flame supervision takes place via an ionization probe or a QRA flame detector with AGQ3.xA27 ancillary unit for forced draft gas burners, or, in the case of blue-burning flames, with a QRC blue-flame detector. In terms of housing dimensions, the LME... are identical with the burner control LGB… and LMG… burner controls.
Features
- Applications in accordance with EN 676: Automatic forced draft burners for gaseous fuels
- Type-tested and approved in accordance with DIN EN 298
- Undervoltage detection
- Air pressure supervision with functional check of the air pressure switch during startup and operation
- Electrical remote reset facility
- Multicolor indication of fault status and operational status messages
- Limitation of the number of repetitions
- Accurate control sequence thanks to digital signal handling
- Controlled intermittent operation after a maximum 24 hours of continuous operation
Specifications
- Make: Siemens
- Model: LME41.091C2
- Mains voltage: AC 230 V +10%/-15%
- Mains frequency: 50...60 Hz ±6%
- Power consumption: 12 VA
- External primary fuse: (Si) Max. 10 A (slow)
- Mounting position: Optional
- Input current at terminal 12: Max. 5 A
- Weight: Approx. 160g
- Degree of protection: IP40 (to be ensured through mounting)